Standby Silent Perkins Generator 250kVA
Powered by Perkins Engine 1206A-E70TTAG2
Commercial/Rental/Industrial backup power solution Application
50HZ 3-Phase AC400V Industrial Voltage
7.01 Litre 6 cylinder water-cooled Diesel Engine Generator
Output Voltage Options – 50 Hz 3-Phase
- AC220/380, 3-phase, 0.8 pf , 184 kW/ 230 kVa, 349.4 Amps
- AC230/400, 3-phase, 0.8 pf ,184 kW/ 230 kVa, 331.2 Amps
- AC240/415, 3-phase, 0.8 pf, 184 kW/ 230 kVa, 319.9 Amps
POWER RATINGS:
200KW (250 KVA) STANDBY, 184KW (230KVA) PRIME, 3PHASE, 0.8PF, 50HZ
- Perkins engine Reliability:
- The Standby Silent Perkins Generator 250kVA uses the reliable Perkins 1206A-E70TTAG2 6-cylinder in-line diesel engine for maximum reliability.
- Perkins provides one-year warranties for constant-speed engines and two-year warranties for variable-speed models as standard.
- Stable & Continuous Power Output:
- The brushless alternator minimizes the need for service and maintenance. It comes with Class H protection.
- The automatic voltage regulator (AVR) ensures accurate regulation.
- The Mechanical/Electronic governor system keeps the frequency within ±0.25%.
- AC output voltage varies within ±0.5%.
- All-Weather And Low-Noise Enclosure:
- Full load noise rating in Soundproof, weather-resistant, steel housing provides operation at 71dB (A) at 7 meters.
- Completely secure casing ensures safe usage.
- Inbuilt fuel reservoir with clear viewing window, and fuel gauge display on the control panel
- Anti-rust powder coating offers longevity and protection against the elements.
- Digital Control & Instruments:
- Engine instruments such as oil pressure, coolant temp, battery voltage, engine RPM, and fuel level.
- AC Generator instruments include an Amp meter, Volt meter, frequency meter, ammeter phase selection switch, and voltmeter phase selection switch.
- Professional generator control systems from Smartgen, Deepsea, or Comap.
- LCD controller with high visibility, heated screen, and display.
- Complies with IP65 Protection standard, with a functioning temperature range from – 40° to 85° C.
- The Modbus interface RS485 is accessible for the gauge panel and offers further expansion options.
- Indication for DPF cleaning cycle.
- Inspection log record.
- Alarm & Protection:
- The safety system monitors water temperature, engine oil pressure, coolant level, fuel level, speed, and engine start. Warning indicators signal unusual conditions.
- Fuel/water separator. It extracts moisture from fuel, prolonging engine lifespan.
- Emergency switch — when triggered manually, it powers down in any crisis.
Specification of Standby Silent Perkins Generator 250kVA
- Manufacturer – METCL
- Model – P250GF/S
- Clean Diesel Fuel
- Generator Speed – 1500 RPM
- Displacement – 7.01 Litre
- Fuel Consumption at rated 184kW/230KVA Load- 51.0 Litre/h
- Perkins 1206A-E70TTAG2, 226kW, 1500RPM, Turbocharged
- Electronic Isochronous governor
- Industrial-grade cooling system with fan guards and coolant drain extension with in-line valve
- AC Alternator Manufacture – METCL/STAMFORD/Leroy-Somer/Mecc Alte
- AC Alternator 4 Leads, brushless, 100% Copper Windings
- Full load rated Power – 184kW/230kVA
- Rotor and 2/3 pitch winding suppress triple harmonics and guarantee a superior voltage waveform
- Class H Insulation and Self-ventilated drip-proof design
- Electronic automatic voltage regulation (AVR)
- 50 Hz. 1500RPM 3Phase AC400V
- 3-Phase AC380/415/440V etc Multi-voltage as optional
CONSTRUCTION OF Perkins Generator 250kVA:
- SS304 stainless steel anti-theft fasteners used.
- Enclosure & Frame Finish-Anti-corrosion power-coated painting
- Built-in 93.5-gallon (354 Liter) Tank
- Vented/Fuel Fill/Cap
- Fitted with Vibration Mounts on the engine/alternator/radiator
- Dimensions – 3500 x 1130 x 1600 (L x W x H)
- Weight – 2,900 kg